An electrical technician connects a DC battery across the primary winding of an iron-core transformer through a switch. After the switch is closed and a steady current is established in the primary winding, what voltage behavior is observed across the secondary winding?
- AA continuous DC output is maintained as long as primary current flows.
- BA continuous alternating voltage is generated across the secondary terminals.
- A brief voltage pulse occurs when the switch closes, followed by zero output while current remains steady.Answer
- DA constant electrostatic charge accumulates in the core without producing any transient voltage.
Answer
A brief voltage pulse occurs when the switch closes, followed by zero output while current remains steady.
According to Faraday's Law of Electromagnetic Induction, an electromotive force (voltage) is induced in a secondary winding only when there is a changing magnetic flux (). When the switch is initially closed, the current rises from zero to its maximum level, generating an expanding magnetic field that induces a brief voltage pulse. Once the DC current reaches a steady state, the magnetic field stops changing (), causing the induced secondary voltage to drop immediately to zero.
Step-by-Step Solution
Key Concept
Faraday's Law of Electromagnetic Induction and Transformer Operation