An electronics technician is troubleshooting an inoperative single-phase ventilation blower that fails to operate when energized. In what sequence should the technician perform the following diagnostic and repair actions to follow standard, safe troubleshooting procedures from initial assessment to final verification?

  1. 1Verify nominal supply voltage at the main input power terminals using a digital multimeter set to AC voltage.
  2. 2Measure the voltage drop across the closed control switch contacts to determine if the switch is passing power.
  3. 3De-energize the power source and verify zero voltage following lockout/tagout safety procedures.
  4. 4Disconnect at least one motor winding lead and measure the winding resistance with an ohmmeter.
  5. 5Replace the defective motor and re-energize the circuit to verify normal operation.

Cevap

The correct logical sequence is: verify supply voltage at the input terminals, measure the voltage drop across the closed control switch, de-energize and lock out the power source, isolate and measure motor winding resistance with an ohmmeter, and finally replace the defective motor and test operation.
Standard electrical troubleshooting begins with verifying the source power, followed by live circuit voltage checks across active control elements. Once the faulty branch or load is localized, the circuit must be safely de-energized before isolating components for resistance testing. The final step is component replacement followed by an operational verification test.

Adım Adım Çözüm

1
Check the input power supply with a voltmeter.
Confirms whether electrical power is reaching the system.
Eliminates external power failure or tripped upstream breakers before diagnosing internal faults.
2
Check the closed control switch for voltage drop under live conditions.
Determines if the switch contacts are conducting correctly (0 V0\text{ V} drop across good closed contacts; full source voltage across open contacts).
Allows quick live-circuit localization of series circuit faults.
3
Disconnect and lock out the circuit power.
De-energizes the system to establish an electrically safe work condition.
Essential for personnel safety and required before using an ohmmeter, which can be damaged by live voltage.
4
Isolate one winding terminal and measure resistance using an ohmmeter.
Provides an accurate internal resistance reading (infinite ohms indicating an open winding).
Isolating one lead prevents parallel circuit paths from yielding false resistance readings.
5
Replace the faulty motor and restore power to test the unit.
Restores system operation and validates that the root fault is fully resolved.
Every repair procedure concludes with an operational check under normal load conditions.

Anahtar Kavram

Logical Troubleshooting and Safety Sequence