Zorluk: OrtaInductors and Transformers

An auxiliary power transformer on a vessel steps down an input voltage of 440 V AC440\text{ V AC} to 110 V AC110\text{ V AC}. If the secondary winding is connected to a lighting circuit drawing 14 A14\text{ A}, what is the primary current in amperes (A\text{A}), assuming an ideal transformer with zero power losses?

Cevap: 3.5 A

Cevap

The primary current is 3.5 A3.5\text{ A}.
In an ideal transformer with negligible losses, the primary apparent power equals the secondary apparent power (Vp×Ip=Vs×IsV_p \times I_p = V_s \times I_s). Because the transformer reduces voltage from 440 V AC440\text{ V AC} to 110 V AC110\text{ V AC} (a 4:14:1 step-down ratio), the primary winding requires only one-fourth of the secondary current. Multiplying 14 A14\text{ A} by 110440\frac{110}{440} yields 3.5 A3.5\text{ A}.

Adım Adım Çözüm

1
State the ideal transformer power balance equation
Vp×Ip=Vs×IsV_p \times I_p = V_s \times I_s
An ideal transformer operates at 100% efficiency, meaning input power (PpP_p) equals output power (PsP_s).
2
Isolate the unknown primary current variable (IpI_p)
Ip=Is×(VsVp)I_p = I_s \times \left(\frac{V_s}{V_p}\right)
Dividing both sides by the primary voltage (VpV_p) provides the direct formula for primary current.
3
Substitute the given numerical values and calculate
Ip=14 A×(110 V440 V)=14×14=3.5 AI_p = 14\text{ A} \times \left(\frac{110\text{ V}}{440\text{ V}}\right) = 14 \times \frac{1}{4} = 3.5\text{ A}
The voltage is stepped down by a factor of 44, which requires the current to be stepped down by the inverse factor of 44 in the primary circuit relative to the secondary.

Anahtar Kavram

Transformer Voltage and Current Transformation Ratio