An infrastructure manager is auditing the environmental and life-safety controls of a newly built core network distribution facility. The server room relies on a total-flooding clean-agent gaseous fire suppression system to protect high-density switches and fiber interconnects. During a simulated system test, concern is raised regarding structural room integrity and agent containment when the high-pressure gas discharges. Which HVAC and airflow control procedure must be implemented upon fire suppression activation to ensure maximum suppression effectiveness while preventing structural damage?
- Automatically actuate motorized dampers to seal HVAC supply and return ducts while opening dedicated pressure relief vents to manage displacement pressure.Cevap
- BMaintain full capacity operation of the primary HVAC exhaust fans to extract combustion smoke while the clean agent dissipates.
- CSwitch the HVAC system into a high-volume negative pressure mode to draw surrounding ambient air into the room during discharge.
- DEngage auxiliary wet-pipe sprinkler heads simultaneously to cool room boundaries and absorb the expanding gaseous agent.
Cevap
Automatically actuate motorized dampers to seal HVAC supply and return ducts while opening dedicated pressure relief vents to manage displacement pressure.
Clean-agent gaseous fire suppression systems function by rapidly discharging gas into an enclosed space to achieve a specific chemical concentration. Automatically closing HVAC supply and return dampers prevents the agent from diluting or escaping into neighboring zones. Concurrently, opening dedicated pressure relief vents dissipates the sudden rise in room pressure during discharge, safeguarding the structural integrity of walls and ceiling enclosures.
Adım Adım Çözüm
Anahtar Kavram
Clean-Agent Fire Suppression and Environmental HVAC Interlocks
Tahmini Süre:2m 0s